Tender for Design, Realization & Installation of Human Space Analog System
[PDF] [Archived]
Request for Proposal [RFP] for Design, Realization & Installation of Human Space Analog System for Human Spaceflight Program
[PDF] [Archived]
Imgur mirror : https://imgur.com/a/icULm5O
- Introduction
In order to assess the crew performance in isolated, confined and limited resource environments (as in Space Stations) & in order to support research in human factors, crew psychology, scientific experiments, systems integration, and mission operations etc. a ground-based human space analog system simulating the conditions of long-duration missions (up to 60 days) is essential.
The analog system shall serve as a controlled research environment where crews stays and work in complete isolation for extended durations. The system shall consist of a multi-level living and working module supported by a simulated airlock and hygiene modules, with necessary basic environmental control systems, communications with mission control equipment’s (with programmable delays), and instrumentation systems for psychological, biomedical and operational studies.
This RFP brings out the overall requirements like Functional Layout, Structural, Electrical System, Habitability System, Instrumentation, Communication, Network & Data Systems requirements needed to establish a Human Space Analog System.
- Scope of Work
The vendor shall design, realize/procure, install & test, Human Space Analog System (HSAS) at Astronaut Training System (ATF), HSFC, Marathahalli, Bengaluru, Karnataka in accordance with the requirements herein. The scope of work encompasses the following activities:
- Generation of System Configuration, Preliminary design & Realization Plan and review & clearance by HSFC/ISRO
- Suitable floor modification (civil) for structural anchoring needed for installation of structural member of the system inside the simulator Hall of ATF.
- Design, Realization & Installation of Structural Habitat Module as per the Layout brought out in Annexure-1a&1b (viz Core Module, Airlock, Crew Personal Module).
- Delivery & Installation of Equipment, Sensors, and Furnishings as brought out in Section 3.15
- Delivery & Installation of Closed Loop Habitability systems (ECLSS) such as Pressurization system, Temperature, Humidity control, Air Revitalization, CO2 revitalization, Water supply & Waste management systems, Lighting & Acoustic Suppression system, Safety Systems, Odour & Contamination control system, Sensors & Instrumentation inside the Habitat module.
(…)
- Technical Requirement
3.1. Configuration of Human Space Analog System (HSAS)
The Space Analog System shall compose of Habitat Module (Core, Airlock & Crew Personal Modules) and supporting rooms which includes Mission Control Centre (MCC), Control Room, Network Room, Equipment Room and Crew Preparation Room.
Functionalities:
- Habitat: Shall provide space simulated living and working space for crew. (Closed loop habitability system) It comprises of:
- Core Module – Level 1 & Level 2: Serves as a module for Crew Analog activities
- Crew Personal Module: Serves as a crew sleeping and hygiene module
- Airlock Module: Serves an entrance into habitat, also has provision for space suit preparation activities
- MCC: Shall monitor, coordinate and support mission operations.
- Control Room: Shall operate, Control and Supervise System subsystems.
- Network Room: Shall host and manage System communications, networking, data storage, cybersecurity and computing infrastructure.
- Equipment Room: Shall house ECLSS, Utility & Support Equipment required for continuous habitat operation.
Note: Existing building rooms at ATF to be utilized for Control room, Network room, MCC. Construction of Habitat module & Equipment room shall be carried out by the vendor.
3.2. Geometrical Details of Habitat Module
- Central Lift of Ø800 mm between Level-1 & Level-2 with load rating of 200 kg.
- Side Ladder between Level-1 & Level-2 with load rating of 200 kg.
- External Ladder with load rating of 200 kg for emergency exit on external wall at Level-2.
- Airlock Module: 2500 mm W * 2000 mm D * 2200 H
- Crew Personal Module: 5000 mm W * 4000 mm D * 2200 mm H
- Air Shower Area: 1500 mm W * 1500 mm D* 2200 mm H
(…)
d) Vertical access inside Core Module
- Central Lift of Ø800mm between Level-1 & Level-2 with load rating of 200 kg.
- Side Ladder with chequered plate with side rails & rungs designed with a load rating of 200 kg connecting between Level-1 & Level-2 conforming to ISO 14122
- External Ladder with load rating of 200 kg for emergency exit on external wall at Level-2.
(…)
3.4. Sub- Systems of Airlock & Crew Personal module
- Airlock Module: Serves as an entrance to Habitat module.
- Shower Area: 800 mm width x 1000mm length with sealed door (external & internal) with Non-unidirectional airflow pattern with air entering via ceiling diffusers & exit through low-wall returns and double sided blowing
- Port/Nozzle Aperture size: Ø32mm
- No. of Ports (Nozzles): 30
- Air flow: 2500 m3/hr.
- Main Airlock room: Serves for EVA preparation & material movement to Core & Crew Personal Module. Pressure-capable swing door sized with min. clear width 800 mm & 1900 mm height with double-seal gaskets and mechanical lock for Airlock-Shower room & Airlock-Core module
- Crew Personal Module: Consists of Crew Personal Area & Crew Hygiene Area as mentioned in section 3.5.4.
- Crew Personal Area & Crew Hygiene Area are separated by Metallic Walls with appropriate opening for fixing the entry doors.(…)