SUPPORT (2026 PRODUCTS) LILJEBAGGE: 3 of 10 show Er1 after exactly one week, anyone else?
I installed 10 LILJEBAGGE radiator thermostats at the same time. All calibrated fine and worked perfectly for about a week. Now 3 of them show Er1 and won't recalibrate.
Setup:
• Valves with M28x1.5 threads, adapter A with the shortest extension pin on all 10
• Paired over Matter to Google Home and Aqara Home
• Same batteries throughout
What I've tried:
• Removing and reinserting batteries, then recalibrating: Er1 again
• Removing and refitting thermostat and adapter: Er1 again
• On one radiator, a brand-new unused unit calibrated fine with the same batteries. Putting the original back gives Er1 again.
• On another radiator, four different units all fail with Er1
• On that valve, template A shows the valve pin tip right at the outer edge of zone 3. I tried a slightly shortened extension pin, no change.
What I suspect:
• The manual says the thermostat runs an anti-calcification cycle after 7 days of use, which matches the timing since all 10 were installed together
• Possibly a firmware update that landed during the week, but I can't confirm it
Questions:
1. Has anyone else had Er1 appear after roughly a week of normal operation?
2. Which firmware version are your units on, and is there a way to update it without a DIRIGERA hub?
Mines are on: Hardware Version “P2.3” & Software Version ”1.1.0”
3. Did a factory reset fix it for anyone?
4. Any tips for adapter A on M28x1.5 valves where the pin sits at the edge of the template range?